Health care fire watch

Fire Watch in Hospitals and Nursing Homes: CMS Requirements, Policy and Log

When CMS and the Life Safety Code require a fire watch in a hospital or nursing home, how often to tour, what to check and log, and what a policy should cover.

By the PatrolBadges team · Updated · 8 min read

The short answer

Hospitals and nursing homes in Medicare and Medicaid must meet the 2012 edition of the Life Safety Code (NFPA 101), which CMS enforces. A fire watch, or evacuation, is required when the fire alarm is out of service for more than 4 hours in 24 (NFPA 101, 9.6.1.6) or the sprinklers are shut down for more than 10 hours (42 CFR 482.41(b)(8) for hospitals, 483.90(a)(8) for long-term care). State guidance, such as Iowa's and Minnesota's, calls for tours at 30-minute intervals by trained staff with no other duties, recorded in a log.

Why a health care fire watch is different

Most buildings answer to the local fire code official. Hospitals and nursing homes in Medicare and Medicaid also answer to CMS, which requires them to meet the Life Safety Code: 42 CFR 482.41 for hospitals and 42 CFR 483.90 for long-term care both incorporate NFPA 101, 2012 edition. The Iowa State Fire Marshal's fire watch guidance for health care is written "in accordance with the 2012 Life Safety Code & the Centers for Medicaid and Medicare Services (CMS)."

So a facility answers to at least two authorities: the fire code official, and the state survey agency that inspects for CMS. Minnesota's Department of Health says CMS requires a written procedure for fire alarm and sprinkler outages, and "Lack of an acceptable procedure is a citable deficiency."

When a fire watch is required

Fire watch triggers for hospitals and nursing homes. Local rules can be stricter.
RuleSystemTrigger
NFPA 101 (2012), 9.6.1.6Fire alarmOut of service more than 4 hours in a 24-hour period: evacuate or provide an approved fire watch.
NFPA 25 (2011), planned outagesSprinklers and other water-based systemsOut of service more than 10 hours in a 24-hour period: a fire watch is one of four options, with evacuation among them.
42 CFR 482.41(b)(8)Hospital sprinklersShut down for more than 10 hours: evacuate the area affected or establish a fire watch.
42 CFR 483.90(a)(8)Long-term care sprinklersThe same wording, for long-term care facilities.
IFC 901.7, where adoptedAny required fire protection systemNotify the fire department and fire code official immediately; a fire watch where the official requires it.
“When a sprinkler system is shut down for more than 10 hours, the hospital must: (i) Evacuate the building or portion of the building affected by the system outage until the system is back in service, or (ii) Establish a fire watch until the system is back in service.”
— 42 CFR 482.41(b)(8)

Nursing homes follow the same rule: 42 CFR 483.90(a)(8) uses the same words for "the LTC facility." Local codes can be stricter, and under the fire code the call to the fire department is immediate. Confirm the triggers, and how they're cited, with your fire code official and state survey agency.

For alarms, "out of service" means a significant part of the system, not one device. Minnesota, citing the NFPA 101 annex, gives the example of "an entire initiating device, signaling or notification appliance circuit," not a single detector.

How often to tour, and who walks

Health care guidance asks for tighter rounds: every 30 minutes, not every hour.

TopicIowa State Fire Marshal (2016)Minnesota Department of Health (2016)
Interval"in each room once every 30 minutes"Each affected area "checked at not less than 30-minute intervals"
Who"Shall be dedicated" and "trained in fire prevention"Staff or an outside agency such as a security company, who "may have no other duties assigned to them"
Equipment"means to notify the fire department"At least one approved means, such as a 2-way radio or cell phone
Record"Fire watch must be logged appropriately"Tours "documented in a log"
Keep records"Documentation maintained for one year"At least three years, recommended

The NFPA 101 annex, quoted by West Virginia's fire marshal, describes a fire watch as "some special action beyond normal staffing, such as assigning an additional security guard(s) to walk the areas affected." A nurse or aide on their normal assignment isn't a fire watch.

Minnesota also asks for trained staff, reasonable rest breaks, and more than one person where one can't reach every area within 30 minutes.

What to check on each tour

Minnesota's tour list, written for health care:

  • Fire, visible smoke, or a strong smell of smoke or other unwanted odors, reported at once.
  • Portable fire extinguishers in place, unobstructed and working.
  • Corridors and exits free of storage and other obstructions.
  • Exit and stairwell doors clear and fully working.
  • EXIT signs visible and lit.
  • Fire doors, smoke barrier doors and hazardous area doors closed and latched, not tied, wedged or blocked open.
  • Oxygen cylinders and containers not in use stored properly.
  • Electrical hazards reported and fixed.
  • No smoking, cutting, welding or flammable liquids in use, unless the work was preauthorized in a properly fire-separated area.
  • Trash and other unneeded combustibles removed from the building.

While the system is down

Minnesota lists measures to start as soon as you learn a system is out, and keep until it's restored:

  • Tell all staff, and the monitoring company, that the system is out of service.
  • If the alarm's sounders don't work, set up another way to warn staff: bells, whistles, bullhorns or similar.
  • If the fire alarm is out, close all smoke and fire doors, and unlock locked exit doors so people can get out at once.

Iowa's notification list adds the local fire department, the Department of Health, the Fire Marshal and the insurance company. Tag the system at each fire department connection, control valve, fire alarm control unit and annunciator, and when it's restored, tell the same people and remove the tags.

Documentation and how long to keep it

In Minnesota's words, "Almost as important as conducting fire watch tours is documenting the fact that they occurred." For each outage, record:

  • Which system was out, when it went out and when it was restored.
  • Who was notified, and when.
  • Every tour: the time, who walked it, the areas checked, and what was found and done.

Iowa says keep the documentation for one year. Minnesota recommends at least three years, and that at least two people know where the logs are kept, for inspections. Keep them for the longer period unless you're told otherwise.

A fire watch policy outline

Minnesota suggests two written policies, one for a fire alarm outage and one for a sprinkler outage, each tailored to the building. It warns that "using a generic or 'boiler plate' policy could result in a federal deficiency." Each policy should answer:

  1. 01

    When it applies

    Which systems, and which triggers: 4 hours for the alarm, 10 hours for sprinklers, or sooner if your authorities say so.

  2. 02

    Who's in charge

    The impairment coordinator by role, with a backup for nights and weekends.

  3. 03

    Who's notified

    The fire department, state agencies, the insurer, the monitoring company and staff: who makes each call, with the numbers.

  4. 04

    Who walks

    Trained staff or contracted security with no other duties, how many, and how they're relieved for breaks.

  5. 05

    The route and interval

    Every affected area, each checked at least every 30 minutes.

  6. 06

    What's checked

    The tour list above, plus the extra measures while the system is down.

  7. 07

    The log

    What's recorded, who reviews it, where it's kept and for how long.

  8. 08

    Back in service

    Testing, notifications, removing the tags and ending the watch.

Using PatrolBadges for a health care fire watch

Set up a route with a round every 30 minutes around the clock, and a QR code or NFC tag in each area the tour must reach: each wing or smoke compartment, stairwells, the kitchen, laundry, oxygen storage and mechanical rooms. Name checkpoints by area, never by resident, and keep resident details out of notes and photos.

Add tour items as checklist questions, such as "Fire doors closed and latched?", answered OK or Problem. A Problem needs a note and opens an incident. Staff or contracted guards scan with their phone's camera, with no app or account, giving their name or PIN once a shift. You're emailed if a round ends with an area unscanned or hasn't started a few minutes in.

Each day's report prints as the fire watch log, exports to CSV, has a private link, and can be emailed to the administrator each morning. If your authority wants proof that every room was entered, as Iowa's wording suggests, ask whether area checkpoints satisfy them, or put a code on more doors: Pro is $9 a month for 10 checkpoints, and $39 for 40.

This guide is general information, not legal advice. Rules vary by state and code edition: your fire code official and state survey agency have the final word. For fire watch rules outside health care, see fire watch requirements.

Frequently asked questions

What are the CMS fire watch requirements?

Hospitals and long-term care facilities must meet the 2012 Life Safety Code. When sprinklers are shut down for more than 10 hours, they evacuate the affected area or establish a fire watch (42 CFR 482.41(b)(8) and 483.90(a)(8)). A fire alarm out for more than 4 hours in 24 needs the same under NFPA 101 (2012).

When does a nursing home need a fire watch?

When the fire alarm is out of service for more than 4 hours in 24, or the sprinklers for more than 10 hours, unless the area is evacuated. Local fire codes can require one sooner. Confirm the triggers with your fire code official and state survey agency.

How often should a fire watch tour a hospital or nursing home?

Every 30 minutes, in published state guidance. Iowa's State Fire Marshal says the person must be "in each room once every 30 minutes," and Minnesota's Department of Health says each affected area is checked at not less than 30-minute intervals. Ask your authorities if they set a different interval.

Can nursing staff do the fire watch?

Staff can, but not on top of their normal duties. Minnesota says fire watch personnel "may have no other duties assigned to them," and Iowa says the fire watch "Shall be dedicated." Assign extra trained staff, or hire a security company.

What should a nursing home fire watch policy include?

When it applies, who the impairment coordinator is, who's notified, who walks the tours and how often, what they check, and where the log is kept and for how long. Minnesota suggests separate policies for fire alarm and sprinkler outages, tailored to the building, since a generic policy could result in a federal deficiency.

How long should we keep fire watch logs?

Published guidance ranges from one year (Iowa State Fire Marshal) to at least three years (Minnesota Department of Health). Keep them for the longer period unless your state survey agency says otherwise, and make sure at least two people know where they are.

Sources

  1. 1.42 CFR 482.41, Condition of participation: Physical environment · Electronic Code of Federal Regulations
  2. 2.42 CFR 483.90, Physical environment · Electronic Code of Federal Regulations
  3. 3.Fire Watch Plan Guidance (memorandum, October 28, 2016) · Iowa Department of Public Safety, State Fire Marshal Division
  4. 4.Systems Out of Service (June 2016) · Minnesota Department of Health
  5. 5.Fire Watch · West Virginia Office of the State Fire Marshal
  6. 6.International Fire Code 2021 (New Jersey edition), Chapter 9: Fire Protection and Life Safety Systems · UpCodes